GE C30 Instruction Manual page 276

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

INPUTS/OUTPUTS
DIRECT OUT 2 OPERAND
DIRECT INPUT 5 DEVICE ID
DIRECT INPUT 5 BIT NUMBER
DIRECT INPUT 6 DEVICE ID
DIRECT INPUT 6 BIT NUMBER
UR IED 3:
DIRECT OUT 2 OPERAND
DIRECT INPUT 5 DEVICE ID
DIRECT INPUT 5 BIT NUMBER
DIRECT INPUT 6 DEVICE ID
DIRECT INPUT 6 BIT NUMBER
UR IED 2:
DIRECT INPUT 5 DEVICE ID
DIRECT INPUT 5 BIT NUMBER
DIRECT INPUT 6 DEVICE ID
DIRECT INPUT 6 BIT NUMBER
DIRECT OUT 2 OPERAND
DIRECT OUT 3 OPERAND
DIRECT OUT 4 OPERAND
The figure shows the signal flow among the three IEDs.
UR IED 1
5
DIRECT OUT 2 = HYB POTT TX1
In three-terminal applications, both the remote terminals must grant permission to trip. Therefore, at each terminal, direct
inputs 5 and 6 are ANDed in FlexLogic and the resulting operand configured as the permission to trip (
setting).
5.8.7 Teleprotection
5.8.7.1 Overview
The relay provides 16 teleprotection inputs on communications channel 1 (numbered 1-1 through 1-16) and 16
teleprotection inputs on communications channel 2 (on two-terminals two-channel and three-terminal systems only,
numbered 2-1 through 2-16). The remote relay connected to channels 1 and 2 of the local relay is programmed by
assigning FlexLogic operands to be sent via the selected communications channel. This allows the user to create
distributed protection and control schemes via dedicated communications channels. Some examples are directional
comparison pilot schemes and direct transfer tripping. Note that failures of communications channels affect
teleprotection functionality. The teleprotection function must be enabled to utilize the inputs.
5-158
:
"HYB POTT
TX1"
: "2"
: "2" (this is a message from IED 2)
: "2"
: "4" (effectively, this is a message from IED 3)
:
"HYB POTT
TX1"
: "2"
: "2" (this is a message from IED 2)
: "2"
: "3" (effectively, this is a message from IED 1)
: "1"
: "2"
: "3"
: "2"
:
"HYB POTT
TX1"
:
"DIRECT INPUT
5" (forward a message from 1 to 3)
:
"DIRECT INPUT
6" (forward a message from 3 to 1)
Figure 5-76: Signal flow for direct input and output
DIRECT INPUT 5
DIRECT INPUT 6
UR IED 2
DIRECT INPUT 5
DIRECT OUT 2 = HYB POTT TX1
DIRECT OUT 4 = DIRECT INPUT 6
DIRECT OUT 3 = DIRECT INPUT 5
DIRECT INPUT 6
UR IED 3
DIRECT INPUT 5
DIRECT INPUT 6
DIRECT OUT 2 = HYB POTT TX1
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
842717A1.CDR
HYB POTT RX1

Advertisement

Table of Contents
loading

Table of Contents