CONTROL ELEMENTS

5.7.3 Digital elements

SETTINGS  CONTROL ELEMENTS  DIGITAL ELEMENTS  DIGITAL ELEMENT 1(48)
 DIGITAL ELEMENT 1
There are 48 identical digital elements available, numbered 1 to 48. A digital element can monitor any FlexLogic operand
5
and present a target message and/or enable events recording depending on the output operand state. The digital element
settings include a name to be referenced in any target message, a blocking input from any selected FlexLogic operand,
and a timer for pickup and reset delays for the output operand.
DIGITAL ELEMENT 1 INPUT
DIGITAL ELEMENT 1 PICKUP DELAY
is not required, set to "0," To avoid nuisance alarms, set the delay greater than the operating time of the breaker.
DIGITAL ELEMENT 1 RESET DELAY
DIGITAL ELEMENT 1 PICKUP LED
operation of the pickup LED is blocked.
SETTING
DIGITAL ELEMENT 01
FUNCTION:
Enabled = 1
SETTING
DIGITAL ELEMENT 01
INPUT:
Off = 0
SETTING
DIGITAL ELEMENT 01
BLOCK:
Off = 0
Circuit monitoring applications
Some versions of the digital input modules include an active voltage monitor circuit connected across form-A contacts.
The voltage monitor circuit limits the trickle current through the output circuit (see technical specifications for form-A).
5-140
DIGITAL ELEMENT 1
FUNCTION: Disabled
DIG ELEM 1 NAME:
Dig Element 1
DIG ELEM 1 INPUT:
Off
DIG ELEM 1 PICKUP
DELAY:
0.000 s
DIG ELEM 1 RESET
DELAY:
0.000 s
DIG ELEMENT 1
PICKUP LED: Enabled
DIG ELEM 1 BLOCK:
Off
DIGITAL ELEMENT 1
TARGET: Self-reset
DIGITAL ELEMENT 1
EVENTS: Disabled
— Selects a FlexLogic operand to be monitored by the digital element.
— Sets the required time delay from element pickup to element operation. If a pickup delay
— Sets the time delay to reset. If a reset delay is not required, set to "0."
— This setting enables or disabled the digital element pickup LED. When set to "Disabled," the
Figure 5-63: Digital element logic
SETTING
DIGITAL ELEMENT 01
NAME:
AND
RUN
Range: Disabled, Enabled
Range: 16 alphanumeric characters
Range: FlexLogic operand
Range: 0.000 to 999999.999 s in steps of 0.001
Range: 0.000 to 999999.999 s in steps of 0.001
Range: Disabled, Enabled
Range: FlexLogic operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTINGS
DIGITAL ELEMENT 01
PICKUP DELAY:
DIGITAL ELEMENT 01
RESET DELAY:
t
PKP
INPUT = 1
t
RST
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
FLEXLOGIC OPERANDS
DIG ELEM 01 DPO
DIG ELEM 01 PKP
DIG ELEM 01 OP
827042A2.VSD