GE C30 Instruction Manual page 47

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

CHAPTER 3: INSTALLATION
USE OF FORM-A AND SOLID-STATE RELAY OUTPUTS IN HIGH-IMPEDANCE CIRCUITS
For form-A and solid-state relay output contacts internally equipped with a voltage measuring circuit across
NOTE
the contact, the circuit has an impedance that can cause a problem when used in conjunction with external
high-input impedance monitoring equipment such as modern relay test set trigger circuits. These monitoring
circuits can continue to read the form-A contact as being closed after it has closed and subsequently opened,
when measured as an impedance.
The solution is to use the voltage measuring trigger input of the relay test set, and connect the form-A contact
through a voltage-dropping resistor to a DC voltage source. If the 48 V DC output of the power supply is used
as a source, a 500 Ω, 10 W resistor is appropriate. In this configuration, the voltage across either the form-A
contact or the resistor can be used to monitor the state of the output.
Where a tilde "~" symbol appears, substitute the slot position of the module. Where a number sign "#" appears,
substitute the contact number.
NOTE
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, give the
FlexLogic operand driving the contact output a reset delay of 10 ms to prevent damage of the output
contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
Table 3-3: Contact input and output module assignments
~6A module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
~3
Form-C
~4
Form-C
~5a, ~5c
2 Inputs
~6a, ~6c
2 Inputs
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
~6E module
Terminal
Output or
assignment
input
~1
Form-C
~2
Form-C
~3
Form-C
~4
Form-C
~5a, ~5c
2 Inputs
~6a, ~6c
2 Inputs
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
~6B module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
~3
Form-C
~4
Form-C
~5
Form-C
~6
Form-C
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
~6F module
Terminal
Output
assignment
~1
Fast Form-C
~2
Fast Form-C
~3
Fast Form-C
~4
Fast Form-C
~5
Fast Form-C
~6
Fast Form-C
~7
Fast Form-C
~8
Fast Form-C
~6C module
Terminal
Output
assignment
~1
Form-C
~2
Form-C
~3
Form-C
~4
Form-C
~5
Form-C
~6
Form-C
~7
Form-C
~8
Form-C
~6G module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
~3
Form-A
~4
Form-A
~5a, ~5c
2 Inputs
~6a, ~6c
2 Inputs
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
WIRING
~6D module
Terminal
Output
assignment
~1a, ~1c
2 Inputs
~2a, ~2c
2 Inputs
~3a, ~3c
2 Inputs
~4a, ~4c
2 Inputs
~5a, ~5c
2 Inputs
~6a, ~6c
2 Inputs
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
~6H module
Terminal
Output or
assignment
input
~1
Form-A
~2
Form-A
~3
Form-A
~4
Form-A
~5
Form-A
~6
Form-A
~7a, ~7c
2 Inputs
~8a, ~8c
2 Inputs
3-13
3

Advertisement

Table of Contents
loading

Table of Contents