CONTROL ELEMENTS
Latch n
Latch n
type
set
Reset
ON
Dominant
OFF
ON
OFF
Set
ON
Dominant
ON
OFF
OFF
5.7 Control elements
5.7.1 Overview
Control elements are used for control rather than protection. See the Introduction to Elements section at the beginning of
this chapter for information.
5
5.7.2 Selector switch
SETTINGS CONTROL ELEMENTS SELECTOR SWITCH SELECTOR SWITCH 1(2)
SELECTOR SWITCH 1
5-134
Figure 5-59: Non-volatile latch operation table (N = 1 to 16) and logic
Latch n
Latch n
Latch n
reset
on
off
OFF
ON
OFF
OFF
Previous
Previous
State
State
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
Previous
Previous
State
State
ON
OFF
ON
SELECTOR 1 FUNCTION:
Disabled
SELECTOR 1 FULL
RANGE: 7
SELECTOR 1 TIME-OUT:
5.0 s
SELECTOR 1 STEP-UP:
Off
SELECTOR 1 STEP-UP
MODE: Time-out
SELECTOR 1 ACK:
Off
SELECTOR 1 3BIT A0:
Off
SELECTOR 1 3BIT A1:
Off
SELECTOR 1 3BIT A2:
Off
SELECTOR 1 3BIT
MODE: Time-out
SELECTOR 1 3BIT ACK:
Off
CHAPTER 5: SETTINGS
Range: Disabled, Enabled
Range: 1 to 7 in steps of 1
Range: 3.0 to 60.0 s in steps of 0.1
Range: FlexLogic operand
Range: Time-out, Acknowledge
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Time-out, Acknowledge
Range: FlexLogic operand
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL