CHAPTER 5: SETTINGS
Master configRev
Range: 0 to 255 ASCII characters
Default:
This data attribute is provided by the protocol to allow the user to declare changes to the semantic of the data model of
the UR. The intent is that the user changes Master configRev each time that the semantic or data model changes, so
that clients can readily detect the change. A semantic change is a logical node getting a new semantic use; for example,
an instance of logical node CSWI is now serving a different physical switch, or an instance of a logical node PDIS is now
used for another zone. A data model change is a change in the presence of logical nodes, data objects, data attributes,
or instance names.
The scope of Maser configRev is the entire relay configuration as the Master logical device is the root logical device.
Similar settings are provided for the other logical nodes; the scope of these other configRev settings is limited to the
corresponding logical device configuration.
paramRev
Range: -2,147,483,648 to 2,147,483,647 in steps of 1
Default: 0
This data attribute is provided by the protocol to make changes to the settings of the C30 apparent to clients. The
Substation Configuration Tool and UR Setup software advance the value of paramRev each time any setting changes.
The C30 increments the value of parmRev when a setting change is made other than through CID file download.
LLN0.Mod.ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the C30. An "on"
control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to
Forcible, and a "test/blocked" changes it to Isolated.
IEC/MMS TCP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 102
This setting allows the user to change the TCP port number for Manufacturing Message Specification (MMS) connections.
It is recommended that this setting be left at the default value.
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
NOTE
Configuration Type
Range: G2, E3-2.0
Default: G2
This setting specifies the method used to describe GOOSE subscription configuration in SCL. See the UR Series
Communications Guide for details. Basically, in the G2 mode, the CID file contains IED elements for IEDs subscribed to by
this IED containing GOOSE subscription information. In the E3 2.0 mode, the CID file has only one IED element and
GOOSE subscription information is coded in data objects in the standard LGOS logical node used to monitor reception of
the subscribed GOOSE. UR 7.30 or later accepts either mode.
GOOSE
The path is Settings > Product Setup > Communications > IEC 61850 > GOOSE.