GE C30 Instruction Manual page 166

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

PRODUCT SETUP
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Messages >
RxGOOSE1. The following settings are available.
RxGOOSE1 ID
Range: 0 to 129 VisibleString characters
Default:
If the value entered has one or more characters, the goID field of incoming GOOSE messages must exactly match this
5
value for the message to be accepted as a valid RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1
does not check the value received in the goID field.
RxGOOSE1 Dst MAC
Range: any 12 digit hexadecimal number
Default: 00-00-00-00-00-00
Set this setting to the MAC address of the publisher. Only received GOOSE messages having a Media Access Control
(MAC) address equal to this value are accepted as valid RxGOOSE1 messages. An entered address of zero disables
RxGOOSE1.
If the publisher is a UR Series 7.3x device, the setting needs to match the value of the publisher's TxGOOSE Dst MAC
setting.
RxGOOSE1 ETYPE APPID
Range: 0 to 65535 in steps of 1
Default: 0
If the value entered is non-zero, the APPID field of incoming GOOSE messages must exactly match this value for the
message to be accepted as a valid RxGOOSE1 message. If the value entered is zero, RxGOOSE1 does not check the value
received in the APPID field.
If the publisher is a UR Series 7.3x device, the setting needs to match the value of the publisher's TxGOOSE ETYPE APPID
setting.
RxGOOSE1 GoCBRef
Range: 0 to 129 alphanumeric, underscore, slash and period characters, beginning with an alpha character
Default:
The gocbRef field of incoming GOOSE messages must match this value for the message to be accepted as a valid
RxGOOSE1 message. If the entered value is the empty string, RxGOOSE1 is disabled. If not the empty string, the entry
needs to be an ACSI ObjectReference to the publishing control block in the format:
<LDName>/LLN0.<GoCBName>
5-48
Figure 5-13: IEC 61850 RxGOOSE Messages panel
CHAPTER 5: SETTINGS
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL

Advertisement

Table of Contents
loading

Table of Contents