CHAPTER 2: PRODUCT DESCRIPTION
EVENT RECORDER
Capacity:
Time-tag:
Triggers:
Data storage:
DATA LOGGER
Number of channels:
Parameters:
Sampling rate:
Trigger:
Mode:
Storage capacity:

2.4.3 Inputs

FREQUENCY
Nominal frequency setting:
Sampling frequency:
Tracking frequency range:
CONTACT INPUTS
Dry contacts:
Wet contacts:
Selectable thresholds:
Tolerance:
Contacts per common return:
Recognition time:
Debounce time:
Continuous current draw:
CONTACT INPUTS WITH AUTO-BURNISHING
Dry contacts:
Wet contacts:
Selectable thresholds:
Tolerance:
Contacts per common return:
Recognition time:
Debounce time:
Continuous current draw:
Auto-burnish impulse current:
Duration of auto-burnish impulse:
DCMA INPUTS
Current input (mA DC):
Input impedance:
Conversion range:
Accuracy:
Type:
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
1024 events
to 1 microsecond
any element pickup, dropout, or operate; contact input change of state; contact output change
of state; self-test events
in non-volatile memory
1 to 16
any available analog actual value
15 to 3600000 ms in steps of 1
any FlexLogic operand
continuous or triggered
(NN is dependent on memory)
1-second rate:
01 channel for NN days
16 channels for NN days
60-minute rate:
01 channel for NN days
16 channels for NN days
25 to 60 Hz
64 samples per power cycle
20 to 70 Hz
1000  maximum
300 V DC maximum
17 V, 33 V, 84 V, 166 V
±10%
4
< 1 ms
0.0 to 16.0 ms in steps of 0.5
4 mA (when energized)
1000  maximum
300 V DC maximum
17 V, 33 V, 84 V, 166 V
±10%
2
< 1 ms
0.0 to 16.0 ms in steps of 0.5
4 mA (when energized)
50 to 70 mA
25 to 50 ms
0 to –1, 0 to +1, –1 to +1, 0 to 5, 0 to 10, 0 to 20, 4 to 20 (programmable)
379 ±10%
–1 to + 20 mA DC
±0.2% of full scale