E1260 Modbus Mapping - Moxa Technologies ioLogik E1200 Series User Manual

Industrial ethernet remote i/o with 2-port ethernet switch
Hide thumbs Also See for ioLogik E1200 Series:
Table of Contents

Advertisement

ioLogik E1200 Series
Reference
30580
4xxxx Read/Write Registers (Functions 3, 6, 16)
Reference
40033
40545
40546
40547
40548
40561
40563
40565
40567

E1260 Modbus Mapping

0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference
04145
3xxxx Read Only Registers (Function 4)
Reference
31537
31538
31539
31540
31541
31542
Address
Data Type
0x0243
1 word
Address
Data Type
0x0020
1 word
0x0220
1 word
0x0221
1 word
0x0222
1 word
0x0223
1 word
0x0230
2 words
0x0232
2 words
0x0234
2 words
0x0236
2 words
Address
Data Type
0x1030
1 bit
Address
Data Type
0x0600
1 word
0x0601
1 word
0x0602
1 word
0x0603
1 word
0x0604
1 word
0x0605
1 word
Modbus/TCP Default Address Mappings
Description
2: Over Range
3. Under Range
Read AI 3 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
3. Under Range
Description
DO all Value (Ch0–3)
Bit0
= Ch0 DO Value (0=OFF, 1=ON)
Bit3
= Ch3 DO Value (0=OFF, 1=ON)
Bit4 to 15 = reserved
CH0 AI 0 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH0 AI 1 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH0 AI 2 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH0 AI 3 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH AI 0 BO Value (floating point)
CH AI 1 BO Value (floating point)
CH AI 2 BO Value (floating point)
CH AI 3 BO Value (floating point)
Description
Clear Watchdog Alarm
Description
CH0 Read RTD Value
Range 0–65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
CH1 Read RTD Value
Range 0–65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
CH2 Read RTD Value
Range 0–65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
CH3 Read RTD Value
Range 0–65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
CH4 Read RTD Value
Range 0–65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
CH5 Read RTD Value
Range 0–65535, Unit:0.1 (Ohm, Celsius, Fahrenheit)
A-24