Iologik E1260; Iologik E1262 - Moxa Technologies ioLogik E1200 Series User Manual

Industrial ethernet remote i/o with 2-port ethernet switch
Hide thumbs Also See for ioLogik E1200 Series:
Table of Contents

Advertisement

ioLogik E1200 Series

ioLogik E1260

Inputs and Outputs
RTD Inputs: 6 channels
Isolation: 3K VDC or 2K Vrms
RTD Inputs
Input Type:
• PT50, PT100, PT200, PT500 (-200 to 850°C)
• PT1000 (-200 to 350°C)
• Resistance of 310, 620, 1250, and 2200 ohms
Sampling Rate:
• All channels: 12 samples/sec
• Per channel: 2 samples/sec
• Only one channel enabled: 12 samples/sec
Resolution: 0.1°C or 0.1 ohm
Accuracy:
± 0.1% FSR @ 25°C
± 0.3% FSR @ -40 and 75°C
Input Impedance: 625K ohms
Power Requirements
Power Consumption: 110 mA @ 24 VDC
MTBF
(mean time between failures)
Time: 660,260 hrs
Database: Telcordia (Bellcore)

ioLogik E1262

Inputs and Outputs
Thermocouple Inputs: 8 channels
Isolation: 3K VDC or 2K Vrms
Thermocouple Input
Sensor Type: J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C), E (-200 to 900°C), R (-50 to 1600°C),
S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C)
Millivolt Type:
• Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV
• Fault and over-voltage protection: -35 to +35 VDC (power off); -25 to +30 VDC (power on)
Sampling Rate:
• All channels: 12 samples/sec
• Per channel: 1.5 samples/sec
• Only one channel enabled: 12 samples/sec
Resolution: 16 bits
Accuracy:
± 0.1% FSR @ 25°C
± 0.3% FSR @ -40 and 75°C
Input Impedance: 10M ohms
Power Requirements
Power Consumption: 118 mA @ 24 VDC
MTBF
(mean time between failures)
Time: 631,418 hrs
Database: Telcordia (Bellcore)
1-11