E1212 Modbus Mapping - Moxa Technologies ioLogik E1200 Series User Manual

Industrial ethernet remote i/o with 2-port ethernet switch
Hide thumbs Also See for ioLogik E1200 Series:
Table of Contents

Advertisement

ioLogik E1200 Series
Reference
14117
14118
14119
14120
14121
14122
14123
14124
14125
14126
14127
14128

E1212 Modbus Mapping

0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference
DO Channel
00001
00002
00003
00004
00005
00006
00007
00008
00017
00018
00019
00020
00021
00022
00023
00024
DI Channel
00257
00258
00259
00260
00261
00262
00263
00264
00265
00266
00267
00268
00269
00270
Address
Data Type
0x1014
1 bit
0x1015
1 bit
0x1016
1 bit
0x1017
1 bit
0x1018
1 bit
0x1019
1 bit
0x101A
1 bit
0x101B
1 bit
0x101C
1 bit
0x101D
1 bit
0x101E
1 bit
0x101F
1 bit
Address
Data Type
0x0000
1 bit
0x0001
1 bit
0x0002
1 bit
0x0003
1 bit
0x0004
1 bit
0x0005
1 bit
0x0006
1 bit
0x0007
1 bit
0x0010
1 bit
0x0011
1 bit
0x0012
1 bit
0x0013
1 bit
0x0014
1 bit
0x0015
1 bit
0x0016
1 bit
0x0017
1 bit
0x0100
1 bit
0x0101
1 bit
0x0102
1 bit
0x0103
1 bit
0x0104
1 bit
0x0105
1 bit
0x0106
1 bit
0x0107
1 bit
0x0108
1 bit
0x0109
1 bit
0x010A
1 bit
0x010B
1 bit
0x010C
1 bit
0x010D
1 bit
Modbus/TCP Default Address Mappings
Description
CH4 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH5 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH6 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH7 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH8 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH9 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH10 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH11 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH12 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH13 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH14 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH15 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
Description
CH0 DO Value 0: Off 1: On
CH1 DO Value 0: Off 1: On
CH2 DO Value 0: Off 1: On
CH3 DO Value 0: Off 1: On
CH4 DO Value 0: Off 1: On
CH5 DO Value 0: Off 1: On
CH6 DO Value 0: Off 1: On
CH7 DO Value 0: Off 1: On
CH0 DO Pulse Operate Status 0: Off 1: On
CH1 DO Pulse Operate Status 0: Off 1: On
CH2 DO Pulse Operate Status 0: Off 1: On
CH3 DO Pulse Operate Status 0: Off 1: On
CH4 DO Pulse Operate Status 0: Off 1: On
CH5 DO Pulse Operate Status 0: Off 1: On
CH6 DO Pulse Operate Status 0: Off 1: On
CH7 DO Pulse Operate Status 0: Off 1: On
CH0 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH1 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH2 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH3 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH4 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH5 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH6 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH7 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH8 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH9 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH10 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH11 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH12 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH13 DI Counter Operate Status 0: Stop 1: Start(R/W)