User-Defined Modbus Addressing

The input and output address can be configured in a different format on a specific settings page. Check the
Enable User-defined Modbus Addressing box, select the Modbus function, and then configure the start
address of each item.

Default Modbus Address

You can view the default Modbus address for all I/O devices on the Default Modbus Address settings page.
However, only the starting address will be displayed for each item with multiple reference addresses. For
example, if the reference addresses for DI Value start from 10001 and the second DI channel's reference
address is 10002, only the first DI channel's Modbus address of 10001 will be displayed. See the diagram
below.
ATTENTION
Disable the user-defined Modbus addressing function if using the MXIO (.NET) library or Active OPC Server to
control or monitor the ioLogik E1200's I/O status.
3-5
Using the Web Console