E1241 Modbus Mapping - Moxa Technologies ioLogik E1200 Series User Manual

Industrial ethernet remote i/o with 2-port ethernet switch
Hide thumbs Also See for ioLogik E1200 Series:
Table of Contents

Advertisement

ioLogik E1200 Series
3xxxx Read Only Registers (Function 4)
Reference
40025
40026
40027
40028
40029
40030
40031
40032
40041
40043
40045
40047
40049
40051
40053
40055

E1241 Modbus Mapping

0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference
04129
04130
04131
04132
04145
1xxxx Read Only Coils (Function 2)
Reference
14097
14098
14099
14100
14113
14114
14115
14116
Address
Data Type
0x0018
1 word
0x0019
1 word
0x001A
1 word
0x001B
1 word
0x001C
1 word
0x001D
1 word
0x001E
1 word
0x001F
1 word
0x0028
2 words
0x002A
2 words
0x002C
2 words
0x002E
2 words
0x0030
2 words
0x0032
2 words
0x0034
2 words
0x0036
2 words
Address
Data Type
0x1020
1 bit
0x1021
1 bit
0x1022
1 bit
0x1023
1 bit
0x1030
1 bit
Address
Data type
0x1000
1 bit
0x1001
1 bit
0x1002
1 bit
0x1003
1 bit
0x1010
1 bit
0x1011
1 bit
0x1012
1 bit
0x1013
1 bit
Modbus/TCP Default Address Mappings
Description
CH AI 0 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH AI 1 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH AI 2 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH AI 3 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH AI 4 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH AI 5 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH AI 6 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH AI 7 Mode: 1:4-20mA, 2:0-20mA, 4:BO
CH AI 0 BO Value (floating point)
CH AI 1 BO Value (floating point)
CH AI 2 BO Value (floating point)
CH AI 3 BO Value (floating point)
CH AI 4 BO Value (floating point)
CH AI 5 BO Value (floating point)
CH AI 6 BO Value (floating point)
CH AI 7 BO Value (floating point)
Description
CH0 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
CH1 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
CH2 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
CH3 AO Clear P2P Output Safe Status
Write: 1= clear status
Read: always zero
Clear Watchdog Alarm
Description
CH0 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
CH1 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
CH2 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
CH3 AO P2P Connect Status 0=OFFLINE, 1=ONLINE
CH0 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH1 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH2 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH3 AO P2P Output Safe Status 0=Normal, 1=Safe Mode
A-20