ioLogik E1200 Series
ioLogik E1214
Inputs and Outputs
Digital Inputs: 6 channels
Relay Outputs: 6 channels
Isolation: 3K VDC or 2K Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to COM):
• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Common Type: 6 points per COM
Counter Frequency: 250 Hz, power off storage
Digital Filtering Time Interval: Software selectable
Relay Output
Type: Form A (N.O.) power relay
Contact Current Rating:
• Resistive Load: 5 A @ 30 VDC, 250 VAC, 110 VAC
Breakdown Voltage: 500 VAC
Relay On/Off Time: 1500 ms (max.)
Initial Insulation Resistance: 1000 M ohms (min.) @ 500 VDC
Mechanical Endurance: 5,000,000 operations
Electrical Endurance: 100,000 operations @ 5 A resistive load
Contact Resistance: 100 m ohms (max.)
Pulse Output: 0.3 Hz at rated load
Note: Ambient humidity must be non-condensing and remain between 5 and 95%. The relays of the ioLogik
E1214 may malfunction when operating in high condensation environments below 0° Celsius.
Power Requirements
Power Consumption: 188 mA @ 24 VDC
MTBF
(mean time between failures)
Time: 808,744 hrs
Database: Telcordia (Bellcore)
1-8