Moxa Technologies ioLogik E1200 Series User Manual page 98

Industrial ethernet remote i/o with 2-port ethernet switch
Hide thumbs Also See for ioLogik E1200 Series:
Table of Contents

Advertisement

ioLogik E1200 Series
Reference
14115
14116
3xxxx Read Only Registers (Function 4)
Reference
DI Channel
30017
30018
30019
30020
30021
30022
30023
30024
30025
30026
30027
30028
30029
30030
30031
30032
30049
30513
30514
30515
30516
30521
30522
30523
30524
30525
30526
30527
30528
30577
30578
30579
Address
Data Type
0x1012
1 bit
0x1013
1 bit
Address
Data Type
0x0010
1 word
0x0011
1 word
0x0012
1 word
0x0013
1 word
0x0014
1 word
0x0015
1 word
0x0016
1 word
0x0017
1 word
0x0018
1 word
0x0019
1 word
0x001A
1 word
0x001B
1 word
0x001C
1 word
0x001D
1 word
0x001E
1 word
0x001F
1 word
0x0030
1 word
0x0200
1 word
0x0201
1 word
0x0202
1 word
0x0203
1 word
0x208
1 word
0x209
1 word
0x20A
1 word
0x20B
1 word
0x20C
1 word
0x20D
1 word
0x20E
1 word
0x20F
1 word
0x0240
1 word
0x0241
1 word
0x0242
1 word
Modbus/TCP Default Address Mappings
Description
CH2 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
CH3 DO P2P Output Safe Status 0=Normal, 1=Safe Mode
Description
CH0 DI Counter Value Hi- Word (Read only)
CH0 DI Counter Value Lo- Word (Read only)
CH1 DI Counter Value Hi- Word (Read only)
CH1 DI Counter Value Lo- Word (Read only)
CH2 DI Counter Value Hi- Word (Read only)
CH2 DI Counter Value Lo- Word (Read only)
CH3 DI Counter Value Hi- Word (Read only)
CH3 DI Counter Value Lo- Word (Read only)
CH4 DI Counter Value Hi- Word (Read only)
CH4 DI Counter Value Lo- Word (Read only)
CH5 DI Counter Value Hi- Word (Read only)
CH5 DI Counter Value Lo- Word (Read only)
CH6 DI Counter Value Hi- Word (Read only)
CH6 DI Counter Value Lo- Word (Read only)
CH7 DI Counter Value Hi- Word (Read only)
CH7 DI Counter Value Lo- Word (Read only)
DI Value (Ch0–7)
Bit0
= Ch0 DI Value (0=OFF, 1=ON)
Bit7
= Ch7 DI Value (0=OFF, 1=ON)
Bit8 to 15 = reserved
CH0 Read AI RAW Value
CH1 Read AI RAW Value
CH2 Read AI RAW Value
CH3 Read AI RAW Value
CH0 Read AI Scaling Value Hi (float)
CH0 Read AI Scaling Value Low (float)
CH1 Read AI Scaling Value Hi (float)
CH1 Read AI Scaling Value Low (float)
CH2 Read AI Scaling Value Hi (float)
CH2 Read AI Scaling Value Low (float)
CH3 Read AI Scaling Value Hi (float)
CH3 Read AI Scaling Value Low (float)
Read AI 0 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
3. Under Range
Read AI 1 Current Mode Status
0: Normal
1: Burn Out
2: Over Range
3. Under Range
Read AI 2 Current Mode Status
0: Normal
1: Burn Out
A-23
.........