Iologik E1213 - Moxa Technologies ioLogik E1200 Series User Manual

Industrial ethernet remote i/o with 2-port ethernet switch
Hide thumbs Also See for ioLogik E1200 Series:
Table of Contents

Advertisement

ioLogik E1200 Series

ioLogik E1213

Inputs and Outputs
Digital Inputs: 8 channels
Digital Outputs: 4 channels
Digital Input/Output (configurable by jumper): 4 channels
Isolation: 3K VDC or 2K Vrms
Digital Input
Sensor Type: NPN, PNP, and dry contact
I/O Mode: DI or event counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to COM):
• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Common Type: 12 points per COM
Counter/Frequency: 250 Hz, power off storage
Digital Output
I/O Mode: DO or Pulse Output
I/O Type: Source
Current: 500 mA per channel
Voltage: 15 to 30 VDC (12 or 9 VDC configurable by jumper on the 4 DO channels)
Pulse Wave Width/Frequency: 1 ms/500 Hz
Over-Voltage Protection: 45 VDC
Over-Current Limit: 1.5 A per channel @ 25°C
Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
Output Current Rating: 0.5A per channel
Power Requirements
Power Input: 24 VDC nominal, 12 to 36 VDC
Power Consumption: 130 mA typical @ 24 VDC