ioLogik E1200 Series
AI Input: Current Mode
Burn Out mode indicates when the Current AI has burned out. For example, the 4–20 mA Burn Out mode is
defined in the following diagram:
Users can define Burn Out (BO) values (default = 2 mA) for selected ranges. When input values are in the
Burn Out range, raw data will register as 0000h to indicate that the analog input has burned out. The definition
of raw data is as follows:
Burnout Value (BO)
Burnout State
Under Range
Normal Range
Over Range
ATTENTION
When configuring the jumpers to select voltage or current measurement for the AI channels, open the cover by
first removing the screw on the back panel. For details on jumper settings, see the Jumper Settings (DIO
and AI) section in Chapter 2.
0.0 < BO < 4.0
0 ≤ AI < BO mA
BO ≤ AI < 4 mA
4 ≤AI ≤ 20.00 mA
XX > 20.00 mA
3-13
Using the Web Console
User defined (default 2 mA)
S/W output 0000h
S/W output raw data
S/W output raw data until FFFEh
S/W output FFFFh