E1210 Modbus Mapping - Moxa Technologies ioLogik E1200 Series User Manual

Industrial ethernet remote i/o with 2-port ethernet switch
Hide thumbs Also See for ioLogik E1200 Series:
Table of Contents

Advertisement

ioLogik E1200 Series
NOTE
The Modbus/TCP ID of the ioLogik E1200 is set to "1" by default.

E1210 Modbus Mapping

0xxxx Read/Write Coils (Functions 1, 5, 15)
Reference
00257
00258
00259
00260
00261
00262
00263
00264
00265
00266
00267
00268
00269
00270
00271
00272
00273
00274
00275
00276
00277
00278
00279
Address
Data Type
0x0100
1 bit
0x0101
1 bit
0x0102
1 bit
0x0103
1 bit
0x0104
1 bit
0x0105
1 bit
0x0106
1 bit
0x0107
1 bit
0x0108
1 bit
0x0109
1 bit
0x010A
1 bit
0x010B
1 bit
0x010C
1 bit
0x010D
1 bit
0x010E
1 bit
0x010F
1 bit
0x0110
1 bit
0x0111
1 bit
0x0112
1 bit
0x0113
1 bit
0x0114
1 bit
0x0115
1 bit
0x0116
1 bit
Modbus/TCP Default Address Mappings
Description
CH0 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH1 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH2 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH3 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH4 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH5 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH6 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH7 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH8 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH9 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH10 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH11 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH12 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH13 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH14 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH15 DI Counter Operate Status 0: Stop 1: Start(R/W)
CH0 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
0 : Return illegal data value(0x03)
CH1 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
0 : Return illegal data value(0x03)
CH2 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
0 : Return illegal data value(0x03)
CH3 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
0 : Return illegal data value(0x03)
CH4 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
0 : Return illegal data value(0x03)
CH5 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
0 : Return illegal data value(0x03)
CH6 DI Clear Count Value
Read
Always return:0
Write:
1 : Clear counter value
0 : Return illegal data value(0x03)
A-2

Advertisement

Table of Contents
loading

Table of Contents