How to Programme

6 How to Programme
6.1 Programming with MCT 10 Set-up
Software
The frequency converter can be programmed from a PC
via RS-485 COM port by using the MCT 10 Set-up Software.
This software can either be ordered using code number
130B1000 or downloaded from www.danfoss.com/Busines-
sAreas/DrivesSolutions/softwaredownload.
6
6

6.2 Local Control Panel (LCP)

The LCP is divided into 4 functional sections.
A. Display
B. Menu key
C. Navigation keys and indicator lights (LEDs)
D. Operation keys and indicator lights (LEDs)
1
2
3
4
6
10
7
8
9
Illustration 6.1 Local Control Panel (LCP)
A. Display
The LCD-display is back-lit with 2 alphanumeric lines. All
data is displayed on the LCP.
Information can be read from the display.
68
1-20 Motor Power
A
[5] 0.37kW - 0.5HP
Setup 1
Main
Status
Quick
B
Menu
Menu
Menu
Com.
C
On
OK
Warn.
Alarm
Hand
O
Auto
D
On
Reset
13
14
®
VLT
HVAC Basic Drive FC 101 Design Guide
1
Parameter number and name.
2
Parameter value.
3
Set-up number shows the active set-up and the edit set-
up. If the same set-up acts as both active and edit set-up,
only that set-up number is shown (factory setting). When
active and edit set-up differ, both numbers are shown in
the display (set-up 12). The number flashing, indicates the
edit set-up.
4
Motor direction is shown to the bottom left of the display
– indicated by a small arrow pointing either clockwise or
counterclockwise.
5
The triangle indicates if the LCP is in status, quick menu or
main menu.
Table 6.1 Legend to Illustration 6.1
B. Menu key
Press [Menu] to select between status, quick menu or main
menu.
C. Navigation keys and indicator lights (LEDs)
6
Com LED: Flashes when bus communication is communi-
cating.
7
Green LED/On: Control section is working.
8
Yellow LED/Warn.: Indicates a warning.
9
Flashing Red LED/Alarm: Indicates an alarm.
5
10 [Back]: For moving to the previous step or layer in the
navigation structure
11 [
] [
parameters and within parameters. Can also be used for
11
setting local reference.
12
12 [OK]: For selecting a parameter and for accepting changes to
11
parameter settings
11
Table 6.2 Legend to Illustration 6.1
D. Operation keys and indicator lights (LEDs)
On
13
[Hand On]: Starts the motor and enables control of the
frequency converter via the LCP.
NOTICE
15
Terminal 27 Digital Input (5-12 Terminal 27 Digital
Input) has coast inverse as default setting. This
means that [Hand On] does not start the motor if
there is no 24 V to terminal 27. Connect terminal
12 to terminal 27.
14
[Off/Reset]: Stops the motor (Off). If in alarm mode, the
alarm is reset.
15
[Auto On]: Frequency converter is controlled either via
control terminals or serial communication.
Table 6.3 Legend to Illustration 6.1
MG18C502 - Rev. 2013-09-06
] [►]: For maneuvering between parameter groups,