Product Overview
2.8.2 EMC Test Results
2
2
The following test results have been obtained using a system with a frequency converter, a screened control cable, a control
box with potentiometer, as well as a motor screened cable.
RFI Filter Type
H4 RFI filter (Class A1)
0.25-11 kW
3x200-240 V IP20
0.37-22 kW
3x380-480 V IP20
H2 RFI filter (Class A2)
15-45 kW
3x200-240 V IP20
30-90 kW
3x380-480 V IP20
0.75-18.5 kW
3x380-480 V IP54
22-90 kW
3x380-480 V IP54
H3 RFI filter (Class A1/B)
15-45 kW
3x200-240 V IP20
30-90 kW
3x380-480 V IP20
0.75-18.5 kW
3x380-480 V IP54
22-90 kW
3x380-480 V IP54
Table 2.12 Test Results
34
VLT
Conduct emission. Maximum shielded cable length [m]
Industrial environment
EN 55011 Class A2
EN 55011 Class A1
Without
With
Without
external
external
external
filter
filter
filter
25
25
25
25
25
25
50
50
25
25
®
HVAC Basic Drive FC 101 Design Guide
Housing, trades and
light industries
EN 55011 Class B
With
Without
With
external
external
external
filter
filter
filter
50
20
50
20
20
20
10
10
MG18C502 - Rev. 2013-09-06
Radiated emission
Industrial
Housing, trades and
environment
light industries
EN 55011 Class A1
EN 55011 Class B
Without
With
Without
external
external
external
filter
filter
filter
Yes
Yes
Yes
Yes
No
No
No
No
Yes
No
No
Yes
No
Yes
No
Yes
Yes
No
With
external
filter
No
No