Product Overview
2.7.7 Reference Handling
Details for Open Loop and Closed Loop operation.
Intern resource
Relative scalling reference
Preset relative reference
±100%
Input command:
Preset reference 0 ±100%
preset ref bit0, bit1, bit2
Preset reference 1 ±100%
Preset reference 2 ±100%
Preset reference 3 ±100%
Preset reference 4 ±100%
Preset reference 5 ±100%
Preset reference 6 ±100%
Preset reference 7 ±100%
Extern resource 1
Parameter choise:
No function
Reference resource 1,2,3
Analog reference
±200 %
Local bus reference
±200 %
LCP potmeter 0~100 %
+
Extern resource 2
No function
Analog reference
±200 %
Local bus reference
±200 %
LCP potmeter 0~100 %
Extern resource 3
No function
Analog reference
±200 %
Local bus reference
±200 %
LCP potmeter 0~100 %
Illustration 2.21 Block Diagram Showing Remote Reference
The remote reference is comprised of:
•
Preset references
•
External references (analog inputs and serial
communication bus references)
•
The preset relative reference
•
Feedback controlled setpoint
Up to 8 preset references can be programmed in the
frequency converter. The active preset reference can be
selected using digital inputs or the serial communications
bus. The reference can also be supplied externally, most
commonly from an analog input. This external source is
selected by one of the 3 Reference Source parameters
(3-15 Reference 1 Source, 3-16 Reference 2 Source and
3-17 Reference 3 Source). All reference resources and the
bus reference are added to produce the total external
®
VLT
HVAC Basic Drive FC 101 Design Guide
Preset reference
±100%
Y
Relative
reference
=
X
±200%
X+X*Y/100
+
±200%
Input commands:
±200%
Speed up/speed down
External reference in %
MG18C502 - Rev. 2013-09-06
Configuration
mode
Input command:
freeze reference
maxRefPCT
minRefPct
min-max ref
±100%
Freeze
reference &
increase/
decrease
reference
Remote
reference in %
reference. The external reference, the preset reference or
the sum of the 2 can be selected to be the active
reference. Finally, this reference can by be scaled using
3-14 Preset Relative Reference.
The scaled reference is calculated as follows:
(
)
Y
Reference = X + X ×
100
Where X is the external reference, the preset reference or
the sum of these and Y is 3-14 Preset Relative Reference in
[%].
If Y, 3-14 Preset Relative Reference, is set to 0%, the
reference is not affected by the scaling.
2
Speed open
loop
Scale to
Hz
Remote
reference/
setpoint
Process
control
Scale to
process
unit
±200%
Feedback
handling
27
2