Outputs; Relay A Delays; Relays B And C - Danfoss vlt soft starter mcd 500 Operating Manual

Hide thumbs Also See for vlt soft starter mcd 500:
Table of Contents

Advertisement

Parameter Descriptions
3-4 Input A Name
Option:
Starter disable
Controller
PLC
Vibration alarm
3-5 Input A Trip
Option:
Always active* A trip can occur at any time when the soft
Operating only A trip can occur while the soft starter is
Run only
3-6 Input A Trip Delay
Range:
0 s
[0:00–4:00 (min:s)] Sets delay between the input
*
8
8
3-7 Input A Initial Delay
Range:
0 s
[00:00–
*
30:00 (min:s)]
3-8 Remote Reset Logic
Option:
Normally closed*
Normally open

8.4 Outputs

4-1 Relay A Function
Option:
Off
Main
contactor*
Run
Trip
Warning
Low current
flag
High current
flag
64
VLT
Function:
Function:
Selects when an input trip can occur.
starter is receiving power.
running, stopping, or starting.
A trip can only occur while the soft starter is
running.
Function:
activating and soft starter tripping.
Function:
Sets a delay before an input trip can occur.
The initial delay is counted from the time a
start signal is received. The state of the input
is ignored until the initial delay has elapsed.
Function:
Selects whether the remote reset input of the
soft starter (terminals 25, 18) is normally
open or normally closed.
Function:
Selects the function of relay A (normally open).
Relay A is not used
The relay closes when the soft starter receives
a start command and remains closed as long
as the motor receives voltage.
The relay closes when the starter changes to
run state.
The relay closes when the starter trips.
The relay closes when the starter issues a
warning.
The relay closes when the low current flag
activates (parameter 4-10 Low Current Flag).
The relay closes when the high current flag
activates (parameter 4-11 High Current Flag).
Danfoss A/S © 05/2016 All rights reserved.
®
Soft Starter MCD 500
4-1 Relay A Function
Option:
Motor temp
flag

8.4.1 Relay A Delays

The soft starter can be configured to wait before opening
or closing relay A.
4-2 Relay A On Delay
Range:
0 s
[0:00–5:00 (min:s)]
*
4-3 Relay A Off Delay
Range:
0 s
[0:00–5:00 (min:s)]
*

8.4.2 Relays B and C

Parameters 4-4 to 4-9 configure the operation of relays B
and C in the same way as parameters 4-1 to 4-3 configure
relay A. See parameter 4-2 Relay A On Delay and parameter
4-3 Relay A Off Delay for details.
Relay B is a changeover relay.
Relay C is normally open.
4-4 Relay B Function
Option:
Off
Main
contactor
Run*
Trip
Warning
Low current
flag
High current
flag
Motor temp
flag
4-5 Relay B On Delay
Range:
0 s
[0:00–5:00 (min:s)]
*
Function:
The relay closes when the motor temperature
flag activates (parameter 4-12 Motor
Temperature Flag).
Function:
Sets the delay for closing relay A.
Function:
Sets the delay for reopening relay A.
Function:
Selects the function of relay B (changeover).
Relay B is not used.
The relay closes when the soft starter receives a
start command and remains closed as long as
the motor is receiving voltage.
The relay closes when the soft starter changes
to run state.
The relay closes when the soft starter trips.
The relay closes when the soft starter issues a
warning.
The relay closes when the low current flag
activates (parameter 4-10 Low Current Flag).
The relay closes when the high current flag
activates (parameter 4-11 High Current Flag).
The relay closes when the motor temperature
flag activates (parameter 4-12 Motor Temperature
Flag).
Function:
Sets the delay for closing relay B.
MG17K602