Troubleshooting
Display
Low level
Low pressure
Motor overload/
Motor 2 overload
Motor connection tx
10
10
Motor thermistor
Network communication (between
module and network)
No flow
Not ready
78
®
VLT
Soft Starter MCD 500
Possible cause/Suggested solution
Name selected for a programmable input. Refer to Input A trip.
Name selected for a programmable input. Refer to Input A trip.
The motor has reached its maximum thermal capacity.
The following can cause overload:
The soft starter protection settings do not match the motor thermal capacity.
Excessive starts per hour.
Excessive throughput.
Damage to the motor windings.
Resolve the cause of the overload and allow the motor to cool.
Related parameters:
Parameter 1-1 Motor Full Load Current.
Parameter 1-2 Locked Rotor Time.
Parameter 1-3 Start Mode.
Parameter 1-4 Current Limit.
Parameter 7-1 Motor FLC-2.
Parameter 7-2 Locked Rotor Time-2.
Parameter 7-3 Start Mode-2.
Parameter 7-4 Current Limit-2.
Parameter 16-1 Motor Overload.
Where X is 1, 2, or 3.
The motor is not connected correctly to the soft starter for in-line or inside delta use.
Check individual motor connections to the soft starter for power circuit continuity.
Check connections at the motor terminal box.
This trip is not adjustable.
Related parameters:
Parameter 15-7 Motor Connection.
The motor thermistor input has been enabled and:
The resistance at the thermistor input has exceeded 3.6 kΩ for more than 1 s.
The motor winding has overheated. Identify the cause of the overheating and allow the motor
to cool before restarting.
The motor thermistor input has been opened.
NOTICE
If a valid motor thermistor is no longer used, fit a 1.2 kΩ resistor across terminals 05
and 06.
Related parameters:
Parameter 16-9 Motor Thermistor.
The network master has sent a trip command to the soft starter, or there could be a network
communication problem.
Check the network for causes of communication inactivity.
Related parameters:
Parameter 16-11 Network/Comms.
Name selected for a programmable input. Refer to Input A trip.
Check input A (terminals 11 and 16). Check if the soft starter disable function is active. If
parameter 3-3 Input A Function is set to Starter disable and there is an open circuit on terminals 11
and 16, the soft starter does not start.