Specifications

11.2.4 Finger Guard Kit

Finger guards may be specified for personnel safety. Finger
guards fit over the soft starter terminals to prevent
accidental contact with live terminals. Finger guards
provide IP20 protection when correctly installed.
MCD5-0131B to MCD5-0215B: 175G5662.
MCD5-0245B to MCD5-0396B: 175G5730.
MCD5-0469B to MCD5-0961B: 175G5731.
MCD5-245C: 175G5663.
MCD5-0360C to MCD5-0927C: 175G5664.
MCD5-1200C to MCD5-1600C: 175G5665.
NOTICE
To be UL-compliant, the models MCD5-0131B to
MCD5-0396B require finger guards.
11.2.5 Surge Protection Kit (Lightning
Protection)
®
As standard, VLT
Soft Starter MCD 500 rated impulse
withstand voltage is limited to 4 kV. The surge protection
kits protect the system and make the soft starter immune
to high-voltage impulses.
6 kV
175G0100 SPD Surge protection kit for G1.
175G0101 SPD Surge protection kit, G2-G5.
12 kV
175G0102 SPD Surge protection kit for G1.
175G0103 SPD Surge protection kit, G1-G5.
1/L1
1/L1
1/L1
E
Illustration 11.1 System with Surge Protection Kit
MG17K602
Operating Guide
2/T1
M
2/T1
3 ~
2/T1
13
14
K1
Danfoss A/S © 05/2016 All rights reserved.
11
11
85