Electrical Installation
4.3.2 In-line Installation
4.3.2.1 Internally Bypassed
K1
F1
1/L1
3/L2
5/L3
E
K1
Main contactor (optional)
F1
Semiconductor fuses (optional)
Illustration 4.6 In-line Installation, Internally Bypassed
4.3.2.2 Non-bypassed
K1
F1
1/L1
3/L2
5/L3
E
K1
Main contactor (optional)
F1
Semiconductor fuses (optional)
Illustration 4.7 In-line Installation, Non-bypassed
MG17K602
Operating Guide
4.3.2.3 Externally Bypassed
Non-bypassed models have dedicated bypass terminals,
which allow the soft starter to continue providing
protection and monitoring functions even when bypassed
via an external contactor. Connect the bypass contactor to
the bypass terminals and control it by a programmable
output configured to Run (see parameters 4-1 to 4-9).
2/T1
NOTICE
M
4/T2
The bypass terminals on MCD5-0245C are:
3
6/T3
13
The bypass terminals on MCD5-0360C to MCD5-1600C
14
are:
K1
If necessary, the fuses can be installed on the input side.
2/T1
4/T2
M
3
6/T3
13
14
K1
K1
K2
F1
Danfoss A/S © 05/2016 All rights reserved.
•
T1B.
•
T2B.
•
T3B.
•
L1B.
•
L2B.
•
L3B.
K2
F1
K1
1/L1
3/L2
5/L3
E
Main contactor
Bypass contactor (external)
Semiconductor fuses (optional)
Illustration 4.8 In-line Installation, Externally Bypassed,
MCD5-0245C
2/T1
T1B
M
4/T2
3
T2B
6/T3
T3B
13
14
K1
33
34
K2
17
4