Specifications
Environmental
Protection
MCD5-0021B to MCD5-0105B
MCD5-0131B to MCD5-1600C
Operating temperature
Storage temperature
Operating altitude (using MCD PC software)
Humidity
Pollution degree
Vibration
Heat dissipation
During start
During run
MCD5-0021B to MCD5-0053B
MCD5-0068B to MCD5-0105B
MCD5-0131B to MCD5-0215B
MCD5-0245B to MCD5-0469B
MCD5-0525B to MCD5-0961B
MCD5-0245C to MCD5-0927C
MCD5-1200C to MCD5-1600C
Certification
C✓
UL/C-UL
MCD5-0021B to MCD5-0396B, MCD5-0245C to MCD5-1600C
MCD5-0469B to MCD5-0961B
MCD5-0021B to MCD5-105B
MCD5-0131B to MCD5-1600C
CE
CCC
Marine
(MCD5-0021B to MCD5-0961B)
RoHS
1) For UL certification extra requirements may apply, depending on the models. For details, see chapter 11.1 UL-compliant Instal-
lation.

11.1 UL-compliant Installation

This section details more requirements and configuration
®
settings for the VLT
Soft Starter MCD 500 to be UL-
compliant. See also Table 4.12.
11.1.1 Models MCD5-0021B to
MCD5-0105B
There are no additional requirements for these models.
11.1.2 Models MCD5-0131B to
MCD5-0215B
Use with finger guard kit, ordering number
175G5662.
Use the recommended pressure terminal/
connector kit. See Table 11.1 for more
information.
MG17K602
Operating Guide
-10 °C (14 °F) to +60 °C (140 °F), above 40 °C (104 °F) with derating
0–1000 m (0–3281 ft), above 1000 m (3281 ft) with derating
11.1.3 Models MCD5-0245B to

11.1.4 Models MCD5-0245C

Danfoss A/S © 05/2016 All rights reserved.
IP20 & NEMA, UL Indoor Type 1
IP00, UL Indoor Open Type
-25 °C (-13 °F) to +60 °C
5–95% relative humidity
≤39 W approximately
≤51 W approximately
≤120 W approximately
≤140 W approximately
≤357 W approximately
4.5 W per ampere approximately
4.5 W per ampere approximately
IP20, when fitted with optional finger guard kit
Lloyds Marine No 1 Specification
Compliant with EU Directive 2002/95/EC
MCD5-0396B
Use with finger guard kit, ordering number
175G5730.
Use the recommended pressure terminal/
connector kit. See Table 11.1 for more
information.
Use the recommended pressure terminal/
connector kit. See Table 11.1 for more
information.
Pollution degree 3
IEC 60068-2-6
4.5 W per ampere
IEC 60947-4-2
1)
UL 508
UL-listed
UL-recognized
IEC 60947-4-2
11
GB 14048-6
83
11