Safety

1
1
1 Safety

1.1 Warnings

The following symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation that could
result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that could
result in minor or moderate injury. It can also be used to
alert against unsafe practices.
NOTICE
Indicates important information, including situations that
can result in damage to equipment or property.
The examples and diagrams in this manual are included
solely for illustrative purposes. The information contained
in this manual is subject to change at any time and
without prior notice. Responsibility or liability is never
accepted for direct, indirect, or consequential damage
resulting from the use or application of this equipment.
NOTICE
Before changing any parameter settings, save the current
parameter to a file using MCD PC Software or the Save
User Set function.
WARNING
ELECTRICAL SHOCK HAZARD
®
VLT
Soft Starters MCD 500 contain dangerous voltages
when connected to mains voltage. Only a qualified
electrician should carry out the electrical installation.
Improper installation of the motor or the soft starter can
cause equipment failure, serious injury, or death. Follow
the guidelines in this manual and local electrical safety
codes.
Models MCD5-0360C ~ MCD5-1600C:
Treat the busbar and heat sink as live parts whenever
the unit has mains voltage connected (including when
the soft starter is tripped or waiting for a command).
6
®
VLT
Soft Starter MCD 500
PROPER GROUNDING
Disconnect the soft starter from mains voltage before
carrying out repair work.
It is the responsibility of the person installing the soft
starter to provide proper grounding and branch circuit
protection according to local electrical safety codes.
Do not connect power factor correction capacitors to the
output of the VLT
factor correction is employed, it must be connected to
the supply side of the soft starter.
IMMEDIATE START
In auto-on mode, the motor can be controlled remotely
(via remote inputs) while the soft starter is connected to
mains.
MCD5-0021B ~ MCD5-961B:
Transportation, mechanical shock, or rough handling
may cause the bypass contactor to latch into the On
state. To prevent the motor from starting immediately on
first commissioning or operation after transportation,
always ensure that the control supply is applied before
the power. Applying control supply before power ensures
that the contactor state is initialized.
SAFETY OF PERSONNEL
The soft starter is not a safety device and does not
provide electrical isolation or disconnection from the
supply.
To provide safety of personnel and equipment, control
the isolation device through an external safety system.
Danfoss A/S © 05/2016 All rights reserved.
WARNING
®
Soft Starter MCD 500. If static power
WARNING
WARNING
If isolation is required, the soft starter must be
installed with a main contactor.
Do not rely on the start and stop functions for
safety of personnel. Faults occurring in the
mains supply, the motor connection, or the
electronics of the soft starter can cause
unintended motor starts or stops.
If faults occur in the electronics of the soft
starter, a stopped motor may start. A temporary
fault in the supply mains or loss of motor
connection can also cause a stopped motor to
start.