Electrical Installation
Model
MCD5-0245C
4
4
MCD5-0360C
MCD5-0380C
MCD5-0428C
MCD5-0595C
MCD5-0619C
MCD5-0790C
MCD5-0927C
MCD5-1200C
MCD5-1410C
MCD5-1600C
Table 4.13 Short Circuit Ratings, Non-bypassed Models
XXX = blade type: See Ferraz/Mersen catalog for details.
1) When protected by any UL-listed fuses or UL-listed circuit breakers sized according to the NEC, models provided with a 3-cycle rating are
suitable for use in a circuit with the prospective current noted.
32
VLT
Nominal
rating [A]
High available
@480 V AC
Maximum fuse
maximum [kA]
255
65
360
65
380
65
430
65
620
65
650
65
790
65
930
65
1200
65
1410
65
1600
65
Danfoss A/S © 05/2016 All rights reserved.
®
Soft Starter MCD 500
Short-circuit ratings
Standard fault current
@600 V AC [kA]
rating [A]
(fuse class)
350 (RK1/J)
18
400 (J)
18
450 (J)
18
450 (J)
30
800 (L)
42
800 (L)
42
1200 (L)
42
1200 (L)
42
1600 (L)
85
2000 (L)
85
2000 (L)
85
Ferraz/Mersen
Ferraz/Mersen
fuse, listed J, L,
fuse, R/C
or RK5 class
semiconductor
fuse
fuses
AJT300
A070URD30XXX
0450
AJT400/RK 5
A070URD33XXX
500
0630
AJT450/RK 5
A070URD33XXX
500
0700
AJT450
A070URD33XXX
0700
A4BQ800
A070URD33XXX
1000
A4BQ800
A070URD33XXX
1000
A4BQ1200
070URD33XXX1
400
A4BQ1200
A070URD33XXX
1400
A4BQ1600
A065URD33XXX
1800
A4BQ2000
A055URD33XXX
2250
A4BQ2500
A055URD33XXX
2500
600 V short-
circuit current
rating [kA]
3 cycles
1)
N/A
MG17K602