7.2.2 Application Set-up Examples

The application set-ups menu makes it easy to configure
the soft starter for common applications. The soft starter
selects the parameters relevant to the application and
suggests a typical setting. Each parameter can be adjusted
to suit the exact requirements.
On the display, the highlighted values are suggested
values. The values indicated by
Always set parameter 1-1 Motor FLC to match the motor
nameplate full load current. The suggested value for motor
FLC is the minimum FLC of the soft starter.
Centrifugal pump
Motor Full Load Current
Start mode
Adaptive start profile
Start ramp time
Stop mode
Adaptive stop profile
Stop time
Table 7.2 Suggested Values for Centrifugal Pump Applications
Submersible pump
Motor Full Load Current
Start mode
Adaptive start profile
Start ramp time
Stop mode
Adaptive stop profile
Stop time
Table 7.3 Suggested Values for Submersible Pump Applications
Damped fan
Motor Full Load Current
Start mode
Current limit
Table 7.4 Suggested Values for Damped Fan Applications
MG17K602
Operating Guide
are the loaded values.
Adaptive control
Early acceleration
10 s
Adaptive control
Late deceleration
15 s
Adaptive control
Early acceleration
5 s
Adaptive control
Late deceleration
5 s
Constant current
350%
Danfoss A/S © 05/2016 All rights reserved.
Undamped fan
Motor Full Load Current
Start mode
Adaptive start profile
Start ramp time
Excess start time
Locked rotor time
Table 7.5 Suggested Values for Undamped Fan Applications
Compressor screw
Motor Full Load Current
Start mode
Start ramp time
Current limit
Table 7.6 Suggested Values for Compressor Screw Applications
Compressor recip
Motor Full Load Current
Start mode
Start ramp time
Current limit
Table 7.7 Suggested Values for Compressor Recip Applications
Conveyor
Motor Full Load Current
Start mode
Start ramp time
Current limit
Stop mode
Adaptive stop profile
Stop time
Table 7.8 Suggested Values for Conveyor Applications
Crusher rotary
Motor Full Load Current
Start mode
Start ramp time
Current limit
Excess start time
Locked rotor time
Table 7.9 Suggested Values for Crusher Rotary Applications
Adaptive control
Constant acceleration
20 s
30 s
20 s
Constant current
5 s
400%
Constant current
10 s
450%
Constant current
5 s
400%
Adaptive control
Constant deceleration
10 s
Constant current
10 s
400%
30 s
20 s