Danfoss vlt soft starter mcd 500 Operating Manual page 52

Hide thumbs Also See for vlt soft starter mcd 500:
Table of Contents

Advertisement

Product Features
5
5
1
Control voltage
2
Remote control inputs
3
Relay outputs
4
3-phase supply
5
Motor terminals
Illustration 5.16 Two-speed Motor Configuration
NOTICE
Contactors K2 and K3 must be mechanically interlocked.
Parameter settings:
Parameter 3-3 Input A Function.
-
-
-
Parameter 4-4 Relay B Function.
-
NOTICE
If the soft starter trips on supply frequency (parameter 16-5 Frequency) when the high-speed signal (7) is removed,
modify the settings of parameters 2-9 to 2-10.
50
®
VLT
F1
1/L1
4
3/L2
5/L3
A4
A5
A6
11
K10
16
15
K1
K2
17
18
S1
25
6
Remote low-speed start input
7
Remote high-speed start input
K10
Remote start relay (low speed)
K11
Remote start relay (high speed)
K1
Line contactor (high speed)
Select Motor Set Select - assigns input A for motor set selection.
Set high-speed performance characteristics using parameters 1-1 to 2-9.
Set low-speed performance characteristics using parameters 7-1 to 7-16.
Select Trip - assigns trip function to relay output B.
Danfoss A/S © 05/2016 All rights reserved.
Soft Starter MCD 500
K3
K2
2/T1
4/T2
6/T3
K1
E
1
K11
K2
21
24
3
K10
K3
22
2
6
7
K2
K3
S1
21, 22,
24
T4
T5
T6
5
T1
T2
T3
K3
K1
K3
K1
K2
K11
K10
K10
K11
Line contactor (low speed)
Star contactor (high speed)
Reset contact
Relay output B
MG17K602