5.10 Emergency Run Operation

®
In normal operation, the VLT
A 2-wire circuit connected to input A (terminals 11, 16) controls emergency run. Closing input A causes the soft starter to
run the motor and ignore all trip conditions.
1
Control voltage (model dependent)
2
24 V DC output
3
Remote control inputs
4
Motor thermistor input (PTC only)
5
Relay outputs
6
3-phase supply
7
Motor terminals
Illustration 5.12 Emergency Run Operation
Parameter settings:
Parameter 3-3 Input A Function.
-
Select Emergency Run - assigns input A to emergency run function.
Parameter 15-3 Emergency Run.
-
Select Enable - Enables the emergency run-mode.