Minimum And Maximum Current Settings; Bypass Contactor; Main Contactor; Circuit Breaker - Danfoss vlt soft starter mcd 500 Operating Manual

Hide thumbs Also See for vlt soft starter mcd 500:
Table of Contents

Advertisement

Electrical Installation

4.5 Minimum and Maximum Current Settings

The minimum and maximum full load current settings depend on the model:
MCD5-0021B
MCD5-0037B
4
4
MCD5-0043B
MCD5-0053B
MCD5-0068B
MCD5-0084B
MCD5-0089B
MCD5-0105B
MCD5-0131B
MCD5-0141B
MCD5-0195B
MCD5-0215B
MCD5-0331B
MCD5-0396B
MCD5-0469B
MCD5-0525B
MCD5-0632B
MCD5-0744B
MCD5-0825B
MCD5-0961B
MCD5-0245C
MCD5-0360C
MCD5-0380C
MCD5-0428C
MCD5-0595C
MCD5-0619C
MCD5-0790C
MCD5-0927C
MCD5-1200C
MCD5-1410C
MCD5-1600C
Table 4.6 Minimum and Maximum Full Load Current

4.6 Bypass Contactor

®
Some VLT
Soft Starter MCD 500 soft starters are internally
bypassed and do not require an external bypass contactor.
Non-bypassed soft starters may be installed with an
external bypass contactor. Select a contactor with an AC1
rating greater than or equal to the full load current rating
of the connected motor.
24
Model
Minimum [A]
Danfoss A/S © 05/2016 All rights reserved.
®
VLT
Soft Starter MCD 500
In-line connection
Maximum [A]
5
23
9
43
10
50
11
53
15
76
19
97
20
100
21
105
29
145
34
170
40
200
44
220
70
350
85
425
100
500
116
580
140
700
164
820
184
920
200
1000
51
255
72
360
76
380
86
430
124
620
130
650
158
790
186
930
240
1200
282
1410
320
1600

4.7 Main Contactor

Install a main contactor if the VLT
connected to the motor in inside delta format and is
optional for in-line connection. Select a contactor with an
AC3 rating greater than or equal to the full load current
rating of the connected motor.

4.8 Circuit Breaker

A shunt trip circuit breaker may be used instead of a main
contactor to isolate the motor circuit in the event of a soft
starter trip. The shunt trip mechanism must be powered
from the supply side of the circuit breaker or from a
separate control supply.
Inside delta connection
Minimum [A]
Maximum [A]
7
34
13
64
15
75
16
79
23
114
29
145
30
150
32
157
44
217
51
255
60
300
66
330
70
525
85
638
100
750
116
870
140
1050
164
1230
184
1380
200
1500
77
382
108
540
114
570
129
645
186
930
195
975
237
1185
279
1395
360
1800
423
2115
480
2400
®
Soft Starter MCD 500 is