Electrical Installation
K1
4
4
K1
Main contactor
K2
Bypass contactor (external)
F1
Semiconductor fuses (optional)
Illustration 4.9 In-line Installation, Externally Bypassed,
MCD5-0360C to MCD5-1600C

4.3.3 Inside Delta Installation

NOTICE
When connecting the VLT
inside delta configuration, always install a main
contactor or shunt trip circuit breaker.
NOTICE
When connecting in inside delta, enter the motor full
load current (FLC) for parameter 1-1 Motor FLC. The MCD
500 automatically calculates inside delta currents based
on this data. Parameter 15-7 Motor Connection is set to
Auto detect as default and can be set to force the soft
starter in inside delta or in-line.
18
VLT
K2
F1
1/L1
2/T1
L1B
3/L2
4/T2
L2B
5/L3
6/T3
L3B
E
13
14
K1
33
34
K2
®
Soft Starter MCD 500 in
Danfoss A/S © 05/2016 All rights reserved.
®
Soft Starter MCD 500

4.3.3.1 Internally Bypassed

K1
M
3
K1
Main contactor
F1
Semiconductor fuses (optional)
Illustration 4.10 Inside Delta Installation, Internally Bypassed

4.3.3.2 Non-bypassed

K1
K1
Main contactor
F1
Semiconductor fuses (optional)
Illustration 4.11 Inside Delta Installation, Non-bypassed
F1
1/L1
2/T
U1(1) U2(4)
3/L2
4/T
V1(2)
W1(3)
5/L3
6/T
E
13
14
K1
F
1/L
2/T
U1(1 U2(4
L1
3/L
4/T
V1(2
L2
W1(
5/L
6/T
L3
E
1
1
K1
M
V2(5)
3
W2(6)
M
V2(5
3
W2(
MG17K602