Parameter
Keypad and
structure
10.62 - 10.71

Stop on Trip Masks

Bit
SP
Coding
1
Default
On (1)
Update rate
Background read
The user can mask some of the trips from tripping the drive. The trip can be completely masked (do nothing in the event of the selected trip) by setting
the trip number into the parameter. The trip can be made to stop the drive and then trip, by enabling the associated bit parameter.
Trips that cannot be masked are UV, AOC, AtL.Err, PS, O.SPd, FOC, O.ht1, O.ht2, O.ht3, EEF, SLX.HF, S.OV, PLL Err, Enc9, SLAVE.Er and HF17 to
HF29.
Example 1.
The user wants the drive to not trip when there is current loss on analog input 2. Enter 28 into Pr 10.52 and set Pr 10.62 to 0.
Example 2.
The user wants the drive to stop and then trip when there is current loss on analog input 2. Enter 28 into Pr 10.52 to achieve this.
10.72

Trip Mask Active

Bit
SP
Coding
1
Range
0 to 1
Default
0
Update rate
Background write
Set to 1 when a trip is being masked.
10.73

Bridge Active

Bit
SP
Coding
Range
0 to 2
Default
0
Update rate
Background write
This parameter will indicate which bridge is on.
"__
"No bridge
"_1
"Bridge 1 active
"2_
"Bridge 2 active
Where _ is a blank.
10.74
Electrical phase back
Bit
SP
Coding
1
Range
0 to 1
Update rate
Background read
When 0 the firing pulses not phased back. When 1 the firing pulses are phased back or the drive disabled.
10.75
Armature voltage clamp active
Bit
SP
Coding
1
Range
0 to 1
Update rate
Background read
Sets to 1 when the armature voltage clamp is activated. Prevents the voltage from increasing further.
When the armature voltage exceeds 1.15 times the supply voltage the armature voltage clamp is activated to prevent the voltage rising. SCR firing is
inhibited until the voltage has fallen.
Mentor MP Advanced User Guide
Issue Number: 4
format
Parameter description
FI
DE Txt VM DP
ND
FI
DE Txt VM DP
ND
FI
DE Txt VM DP
ND
1
FI
DE Txt VM DP
ND
FI
DE Txt VM DP
ND
www.onxcontrol.com
Advanced parameter
descriptions
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
Serial comms
Performance
protocol
PS
PS
PS
1
PS
PS
Menu 10