Drive Output Is At Current Limit; Direction Commanded; Overload Alarm; Drive Warning/Drive Over Temperature Alarm - Emerson Mentor MP Advanced User's Manual

High performance dc drive 25a to 7400a, 480v to 690v
Hide thumbs Also See for Mentor MP:
Table of Contents

Advertisement

Parameter
Keypad and
structure
10.09

Drive output is at current limit

Bit
SP
Coding
1
Update rate
4 ms write
Indicates that the current limits are active.
10.10
Regenerating
Bit
SP
Coding
1
Update rate
4 ms write
Indicates that power is being transferred from the motor to the supply.
10.13

Direction commanded

Bit
SP
Coding
1
Update rate
Background write
This parameter is one if the pre-ramp reference (Pr 1.03 = {di02, 0.37}) is negative, and zero if the pre-ramp reference is zero or positive.
10.14
Direction running
Bit
SP
Coding
1
Update rate
Background write
This parameter is one if the speed feedback (Pr 3.02 = {di05, 0.40}) is negative, or zero if the speed feedback is zero or positive.
10.17

Overload alarm

Bit
SP
Coding
1
Update rate
Background write
This parameter is set if the drive output current is larger than 105 % of rated current (Pr 5.07 = {SE07, 0.28}) and the overload accumulator is greater
than 75 % to warn that if the motor current is not reduced the drive will trip on an Ixt overload. (If the rated current (Pr 5.07 = {SE07, 0.28}) is set to a
level above the rated drive current (Pr 11.32) the overload alarm is given when the current is higher than 100 % of rated current.)
10.18
Drive over temperature alarm
Bit
SP
Coding
1
Update rate
Background write
Indicates that the heat sink temperature Pr 7.04 is above the alarm level.
10.19
Drive warning
Bit
SP
Coding
1
Update rate
Background write
Indicates that one of the drive alarms is active, i.e. Pr 10.19 = Pr 10.17 OR Pr 10.18.
Mentor MP Advanced User Guide
Issue Number: 4
format
Parameter description
FI
DE
Txt
VM DP
ND
1
FI
DE
Txt
VM DP
ND
1
FI
DE
Txt
VM DP
ND
1
FI
DE
Txt
VM DP
ND
1
FI
DE
Txt
VM DP
ND
1
FI
DE
Txt
VM DP
ND
1
FI
DE
Txt
VM DP
ND
1
www.onxcontrol.com
Advanced parameter
descriptions
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
Serial comms
Performance
protocol
PS
PS
PS
PS
PS
PS
PS
Menu 10
131

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents