Parameter
Keypad and
structure
12.04
Threshold detector 1 level
12.24
Threshold detector 2 level
Bit
SP
Coding
Range
0.00 to 100.00 %
Default
0.00
Update rate
4 ms x number of menu 9 or 12 functions active read
12.05
Threshold detector 1 hysteresis
12.25
Threshold detector 2 hysteresis
Bit
SP
Coding
Range
0.00 to 25.00 %
Default
0.00
Update rate
4 ms x number of menu 9 or 12 functions active read
12.06
Threshold detector 1 output invert
12.26
Threshold detector 2 output invert
Bit
SP
Coding
1
Default
0
Update rate
4 ms x number of menu 9 or 12 functions active read
12.07
Threshold detector 1 destination
12.27
Threshold detector 2 destination
Bit
SP
Coding
Range
Pr 0.00 to Pr 22.99
Default
Pr 0.00
Update rate
Read on reset
The threshold detector compares the absolute value of the source input value (defined by Pr 12.03, Pr 12.23), converted to a percentage of its
maximum value, with the threshold level (Pr 12.04, Pr 12.24). If the value is greater or equal to the threshold plus half the hysteresis band (Pr 12.05,
Pr 12.25) the output becomes active, or if the value is less than the threshold minus half the hysteresis band the output becomes inactive. The output
may be inverted if required by setting the invert flag (Pr 12.06, Pr 12.26). The result is routed to the destination (defined by Pr 12.07, Pr 12.27).
Mentor MP Advanced User Guide
Issue Number: 4
format
Parameter description
FI
DE Txt VM DP
ND
2
FI
DE Txt VM DP
ND
2
FI
DE Txt VM DP
ND
FI
DE Txt VM DP
ND
1
2
www.onxcontrol.com
Advanced parameter
descriptions
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
RA NC NV
PT
US RW BU
1
1
1
Serial comms
Performance
protocol
PS
1
PS
1
PS
PS
1
Menu 12