Parameter
Menu 7
structure
7.24
T10 analog output 2 mode
Bit
SP
Coding
Range
0 to 3
Default
0
Update rate
Background read
See Pr 7.21 description.
7.28
T7 analog input current loop loss 2
7.29
T8 analog input current loop loss 3
Bit
SP
Coding
1
Update rate
Background write
If an analog input is used with 4-20 mA or 20-4 mA current loop modes the respective bit (Pr 7.28 - analog input 2 and Pr 7.29 -analog input 3) is set
to one if the current falls below 3 mA. If the current is above 3 mA with these modes or another mode is selected the respective bit is set to zero.
7.30
T5/6 analog input 1 offset
Bit
SP
Coding
Range
±100.00 %
Default
0.00
Update rate
Background read
7.31
T7 analog input 2 offset
7.32
T8 analog input 3 offset
Bit
SP
FI
Coding
Range
±100.0 %
Default
0.0
Update rate
Background read
An offset can be added to each analog input with a range from -100 % to 100 %. If the sum of the input and the offset exceeds ±100 % the results is
limited to ±100 %.
7.34
SCR / thyristor junction temperature
Bit
SP
Coding
o
Range
0 to 150 C
Update rate
Background read
This parameter is an estimate of the SCR / thyristor junction temperature. If the value rises above 120
114
Keypad and
FI
DE
TE
VM DP
ND
1
FI
DE
TE
VM DP
ND
1
FI
DE
TE
VM DP ND
2
DE
TE
VM DP
ND
1
FI
DE
TE
VM DP
ND
1
www.onxcontrol.com
Advanced parameter
format
Parameter description
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC
NV
PT
US RW BU
1
1
RA
NC NV
PT
US
RW BU PS
1
1
RA
NC
NV
PT
US RW BU
1
1
Serial comms
protocol
descriptions
PS
1
PS
PS
PS
1
o
C, the drive will trip O.ht1.
Mentor MP Advanced User Guide
Performance
Issue Number: 4