Parameter
Description
Aux1 Trip Function
Auxiliary 1 Trip Function
Aux1 Alarm
Auxiliary 1 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function1 =
Use
Aux1 t-Delay
Auxiliary 1 If this time is expired a Temperature Alarm will
be generated.
Only available if: Device Planning: Alarm Function1 =
Use
Aux1 Trip
Auxiliary 1 Threshold for Temperature Trip
Only available if: Device Planning: Trip Function2 = Use
Aux2 Alarm
Auxiliary 2 Alarm Function
Function
Aux2 Trip Function
Auxiliary 2 Trip Function
Aux2 Alarm
Auxiliary 2 Threshold for Temperature Alarm
Only available if: Device Planning: Alarm Function2 =
Use
EMR-4000
Setting range
Inactive,
Active
0 - 200°C
0 - 360min
0 - 200°C
Inactive,
Active
Inactive,
Active
0 - 200°C
www.eaton.com
IM02602009E
Default
Menu path
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
1min
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
100°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux1]
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]
Active
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]
80°C
[Protection Para
/<1..4>
/Temp-Prot
/RTD
/Aux2]