Setting Group Parameters of the Underload Module
Parameter
Description
Function
Permanent activation or deactivation of module/element. Inactive,
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Blo TripCmd
Permanent blocking of the Trip Command of the
module/element.
ExBlo TripCmd Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo TripCmd Fc=active".
Underload
Underload Pickup based on a multiplier of FLA
Phases
Indicates if one, two of three or all phases are required
for operation
t
Tripping delay
EMR-4000
Setting range
Active
Inactive,
Active
Inactive,
Active
Inactive,
Active
0.05 - 0.90FLA
any one,
all
0.4 - 1200.0s
www.eaton.com
IM02602009E
Default
Menu path
Inactive
[Protection Para
/<1..4>
/Underload-Prot
/37[1]]
Inactive
[Protection Para
/<1..4>
/Underload-Prot
/37[1]]
37[1]: Inactive
[Protection Para
37[2]: Active
/<1..4>
37[3]: Inactive
/Underload-Prot
/37[1]]
Inactive
[Protection Para
/<1..4>
/Underload-Prot
/37[1]]
0.50FLA
[Protection Para
/<1..4>
/Underload-Prot
/37[1]]
any one
[Protection Para
/<1..4>
/Underload-Prot
/37[1]]
37[1]: 10.0s
[Protection Para
37[2]: 10.0s
/<1..4>
37[3]: 0.4s
/Underload-Prot
/37[1]]