Device Planning Parameters of the Power Protection Module
Parameter
Description
Mode
Mode
Global Protection Parameters of the Power Protection Module
Parameter
Description
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
ExBlo TripCmd
External blocking of the Trip Command of the module/the
element, if blocking is activated (allowed) within a
parameter set and if the state of the assigned signal is
true.
EMR-4000
Options
Do not use,
Over forward,
Over reverse,
Under forward,
Under reverse
Setting range
1..n, Assignment
List
1..n, Assignment
List
1..n, Assignment
List
www.eaton.com
Default
Menu path
32[1]: Over
[Device Planning]
forward
32[2]: Under
forward
32[3]: Over
reverse
Default
Menu path
-.-
[Protection Para
/Global Prot Para
/Power-Prot
/32[1]]
-.-
[Protection Para
/Global Prot Para
/Power-Prot
/32[1]]
-.-
[Protection Para
/Global Prot Para
/Power-Prot
/32[1]]
IM02602009E
656