Eaton EMR-4000 Installation, Operation And Maintenance Manual page 595

Motor relay
Table of Contents

Advertisement

Criterion - Measuring Method
For all protection elements it can be determined, whether the measurement is done on basis of the » Fundamental« or if
» True RMS« measurement is used.
Dropout Ratio
The dropout ratio is settable.
If phase voltages are applied to the measuring inputs of the device and field parameter
»Main VT con« is set to »Wye« , the messages issued by the voltage protection module in
case of actuation or trip should be interpreted as follows:
»59M[1].P
A« or »59M[1].T
ICKUP
»59M[1].P
B« or »59M[1].T
ICKUP
»59M[1].P
C« or »59M[1].T
ICKUP
However,if line-to-line voltages are applied to the measuring inputs and field parameter
»Main VT con« is set to »Wye« , then the messages should be interpreted as follows:
»59M[1].P
A« or »59M[1].T
ICKUP
»VAB« .
»59M[1]. P
B« or »59M[1].T
ICKUP
»VBC« .
»59M[1]. P
C« or »59M[1].T
ICKUP
»VCA«
EMR-4000
A« => pickup or trip caused by phase voltage »VA« .
RIP
B« => pickup or trip caused by phase voltage »VB« .
RIP
B« => pickup or trip caused by phase voltage »VC« .
RIP
A« => pickup or trip caused by line-to-line voltage
RIP
B« => pickup or trip caused by line-to-line voltage
RIP
C« => pickup or trip caused by line-to-line voltage
RIP
www.eaton.com
IM02602009E
595