Parameter
Description
Curve Shape
Characteristic
t-multiplier
Time multiplier/tripping characteristic factor. The setting
range depends on the selected tripping curve.
Reset Mode
Reset Mode
t-reset
Reset time for intermittent phase failures (INV
characteristics only)
Available if:Reset Mode = t-delay
VRestraint
Voltage Restraint Protection
EMR-4000
Setting range
IEC NINV,
IEC VINV,
IEC EINV,
IEC LINV,
ANSI MINV,
ANSI VINV,
ANSI EINV,
Therm Flat,
IT,
I2T,
I4T
0.02 - 20.00
Instantaneous,
t-delay,
Calculated
0.00 - 60.00s
Inactive,
Active
www.eaton.com
IM02602009E
Default
Menu path
ANSI MINV
[Protection Para
/<1..4>
/I-Prot
/51P[1]]
51P[1]: 1
[Protection Para
51P[2]: 2
/<1..4>
51P[3]: 3
/I-Prot
/51P[1]]
Calculated
[Protection Para
/<1..4>
/I-Prot
/51P[1]]
0s
[Protection Para
/<1..4>
/I-Prot
/51P[1]]
Inactive
[Protection Para
/<1..4>
/I-Prot
/51P[1]]
507