Automation Units and Automation Networks
6.2.4
SICAM AK 3 as Telecontrol Substation with integrated Switch for
External System connection
·
Communication with the control system via IEC 60870-104
(Ethernet-Interface, X0 or X1, can be set with parameter)
·
Communication with the external system via IEC 60870-104
(Ethernet-Interface, X0 or X1, can be set with parameter)
·
SICAM AK 3 is used as switch between control system and external system
Features of the Ethernet Ports:
·
1 IP address
·
1 subnet mask
·
1 default router
·
Parameter
─ 1 IP address (connected ports in switch mode)
Office Zone
Control Center Zone
Substation Zone
SICAM AK 3
248
Network settings | IP address | Mode of Ethernet ports
S I C A M A K
S I C A M A K
Control Center
IP-address:
Subnet mask: 255.255.0.0
Router
IP-address:
172.16.0.254
CP-2016 or CP-2019
PRE0 / ET24
IP-address: 172.16.0.3
Subnet mask: 255.255.0.0
Default router: 172.16.0.254
X0
X1
X2
X3
IP-address:
172.16.0.4
External
Subnet mask: 255.255.0.0
device
Default router: 172.16.0.254
SICAM RTUs, SICAM AK 3 User Manual
Edition 07.2016, DC2-028-2.03
172.17.0.22