Service
5.2.3
Peripheral Elements
Startup (step)
Reset, power up or startup initiat-
ed by the higher-level system
element
Check code memory (flash
PROM)
Check data memory (RAM)
Reception of the parameters from
the higher-level system element
Check of the parameter contents
Startup concluded without error
Startup concluded with error
*)
in addition the system-LED "ER" lights up on the basic system element
Error (startup aborted)
Module defect
PROM error (code)
RAM error (data)
Too little memory
Parameter error
*)
in addition the system-LED "ER" lights up on the basic system element
Error (startup continued)
Parameter error
*)
in addition the system-LED "ER" lights up on the basic system element
218
RY
ER
Error
™
*)
˜
Module defect
™
*)
PROM error
(code)
˜
· Module is shutdown
· Startup is aborted
™
*)
˜
RAM error
(data)
· Module is shutdown
· Startup is aborted
™
*)
Too little memory
™
· Firmware is shutdown
· Startup is aborted
™
*)
™
Parameter
error
· Diagnosis information is set
˜
™
˜
˜
RY
ER
Note
™
*)
˜
Exchange system element
™
*)
Exchange system element
˜
™
*)
Exchange system element
˜
™
*)
§
SICAM TOOLBOX II diagnosis
™
*)
˜
SICAM TOOLBOX II diagnosis
RY
ER
Note
˜
*)
˜
SICAM TOOLBOX II diagnosis