Siemens SICAM RTU User Manual page 241

Table of Contents

Advertisement

·
Each bus interface module CM-0842 has to be supplied separately.
(18 VDC ... 78 VDC)
·
Settings A on the Configuration switch CM-0842
1 F1/F2 ON
2 LINE2 OFF
3 AS2
4 AS1
5 AS0
6 RED OFF
7 LAD
8 LINE1 OFF
·
Settings B on the Configuration switch CM-0842
1 F1/F2 ON
2 LINE2 ON
3 AS2
4 AS1
5 AS0
6 RED OFF
7 LAD
8 LINE1 OFF
Necessary modules and cables
SICAM AK 3
CP-2016
Master control element CP-2016/CPCX26
Basic unit
CP-2019
Processing and communication element CP-
2019/PCCX26
Cable •
Patch cable CAT5 (4x2) AWG26/7
Bus Interface Mod-
CM-0842 Ax 1703-bus interface 4x FO
ule
Cable ‚
FO-INDOORCABLE-200-DUP-BREAK-ROUND
FO-CONNECTOR-ODLP-200 (2 pcs. per connection)
FO-OUTDOORCABLE-200-2FIB-ARM
FO-CONNECTOR-ODLP-200 (2 pcs. per connection)
FO-PIPE SPLITTER 2Y-LR1 (2 pcs. per connection)
(only for outdoorcableTF7-036)
Peripheral elements
PE-6411 peripheral coupling Ax-bus 1x optical
SICAM TM
SICAM RTUs, SICAM AK 3 User Manual
DC2-028-2.03, Edition 07.2016
16 MBit
PE(A)
OFF
0
OFF
0
OFF
0
CM-0842
OFF
inactive
PE
16 MBit
BSE(E)
OFF
0
OFF
0
OFF
0
CM-0842
OFF
inactive
PE
Designation
Automation Units and Automation Networks
Item-Number/MLFB
BC2-016 / 6MF10130CA160AA0
BC2-019 / 6MF10132CA100AA0
T41-255 (1m) / 6MF13040BC550AA0
T41-251 (2m) / 6MF13040BC510AA0
T41-252 (3m) / 6MF13040BC520AA0
GA0-842 / 6MF11110AJ420AA0
TF7-035 TF7-015
TF7-036 TF7-015 TF7-066
GC6-411 / 6MF11130GE110AA0
241

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sicam ak 3

Table of Contents