Sicam Ak 3 As Telecontrol Substation With Node Function (Protocol Converter) - Siemens SICAM RTU User Manual

Table of Contents

Advertisement

6.2.3
SICAM AK 3 as Telecontrol Substation with Node Function (Pro-
tocol Converter)
·
Communication with the control system via IEC 60870-104
(Ethernet-Interface, X0 or X1, can be set with parameter)
·
Communication with the protective devices via IEC 61850
(Ethernet-Interface, X0 or X1, can be set with parameter)
Features of the Ethernet Ports:
·
2 IP addresses
·
2 logically separated subnets
─ Communication only visible on the LAN within the subnet
─ data exchange between subnets only via SICAM AK 3 application function
·
1 default router
·
Parameter
2 IP addresses (independent ports)
·
Both Ethernet interfaces (X0, X1) have the same MAC address
Office Zone
Control Center Zone
Substation Zone
SICAM AK 3
S I C A M A K
SICAM RTUs, SICAM AK 3 User Manual
DC2-028-2.03, Edition 07.2016
Network settings | IP address | Mode of Ethernet ports
Note
In case of IP address = 0.0.0.0, the corresponding port is deactivated.
S I C A M A K
Automation Units and Automation Networks
Control Center
IP-address:
Subnet mask: 255.255.0.0
Router
IP-address:
172.16.0.254
CP-2016 or CP-2019
PRE0 / ET24
IP-address:
Subnet mask: 255.255.0.0
Default router: 172.16.0.254
X0
X1
X2
X3
PRE1 / ET24
IP-address:
Subnet mask: 255.255.255.0
Default router: 172.16.0.254
172.17.0.22
172.16.0.3
192.168.1.130
IP-address:
192.168.1.n
247