UPS Startup for 208V-240V Models

To start up the UPS for 208V, 220V, 230V, or 240V models:
Powerware
®
Prestige Series Installation and Operator's Manual for IBM Applications (650 VA - 1500 VA) Uncontrolled Copy
4. The equipment to be protected by the UPS should be powered
off. Plug the equipment into the power output receptacles on
the UPS rear panel.
Do not protect laser printers with the UPS because of the
exceptionally high cyclic power requirements of the heating
elements.
5. For the AS/400 interface, plug the AS/400 communications
cable into the serial port on the UPS rear panel. Plug the other
end of the cable into the connector, located on the back of the
system unit, labeled "UPS" (AS/400 Models 2xx/4xx/170).
6. Turn on the equipment that is connected to the UPS.
7. Press and hold the Output On button until you hear the UPS
beep (approximately one second).

The
indicator remains lit and the Self Test indicator turns
on. The front panel displays the percentage of full load being
applied to the UPS. The UPS is now in Normal mode with the
load online. See "Normal Mode" on page 50 for more
information.
8. The installation is complete. Continue to Chapter 4, "UPS
Operation" on page 49 for more information on the UPS.
1. If you are connecting the UPS to an AS/400, the QUPSDLYTIM
system value for the UPS Monitoring feature should be set. See
"UPS Monitoring" on page 54 for instructions.
2. Steps 3 through 8 are for changing the output voltage. The
output voltage is factory-configured for 230V. If you do not
need to change the output voltage, skip to Step 9.
Installation
39