Instruction manual
MTL intrinsic safety solutions
MTL 9493-PS-XXX
Intrinsically safe power supply
October 2016
INM MTL 9493-PS-XXX Rev 2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MTL 9493-PS Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Eaton MTL 9493-PS Series

  • Page 1 Instruction manual October 2016 MTL intrinsic safety solutions INM MTL 9493-PS-XXX Rev 2 MTL 9493-PS-XXX Intrinsically safe power supply...
  • Page 2: Declaration Of Conformity

    DECLARATION OF CONFORMITY A printed version of the Declaration of Conformity has been provided separately within the original shipment of goods. However, you can find a copy of the latest version at http://www.mtl-inst.com/certificates INM 9493-PS-XXX Rev 2...
  • Page 3: Table Of Contents

    CONTENTS DECLARATION OF CONFORMITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II GENERAL SAFETY INFORMATION .
  • Page 4: General Safety Information

    No changes to any of the components that might impair their explosion protection are permitted. If any information provided here is not clear: Contact Eaton’s MTL product line or an authorised distributor or sales office. NOTE Improper installation and operation of the enclosure can result in the invalidation of the guarantee .
  • Page 5: Features

    MTL 9493-PS-XXX IS Power Supply FEATURES • Isolated power supply • Zone 2 mountable • DIN-rail or backplane mounting • ATEX / IECEx approvals • Range of Ex ia output voltages available • Power over Ethernet option (PoEx)* • Multiple outputs achieved by ganging MTL 9493-PS-XXX modules using 24V DC power distribution backplane *Note –...
  • Page 6: Din-Rail Installation Method

    Hazardous area Safe area Zone 0 Figure 2 .1 Zone 0 Ex ia IIB application – 946x-ET Vs– device See connection tables Terminal Function Ex ia output +ve Table 2 .1 n.c. DIN-rail Ex ia output –ve mounting Supply –ve (Vs–) connections Supply +ve (Vs+) Terminal...
  • Page 7: Protection Of Equipment

    This section deals with mounting the individual MTL 9493-PS-XXX power supplies on DIN rail, for backplane mounting see Section 4. WARNING ! If this module is to be connected to intrinsically safe apparatus, it must be installed, operated and maintained only be trained competent personnel and in accordance with all appropriate international, national and local standard codes of practice and site regulation and in accordance with the instructions contained here.
  • Page 8: Mounting Power Supplies On Din Rail

    3 .2 . 1 Mounting power supplies on DIN rail Clip power supplies onto type T35 DIN rail as shown in Figure 3.2, with the blue signal plugs facing towards the hazardous-area wiring. To remove an power supply from the rail, insert a screwdriver blade into the clip as shown and lever the clip gently outwards;...
  • Page 9: Ambient Temperature Considerations

    Finishing Wire up individual power supplies in accordance with wiring schedules. Daisy-chain power supply connections between individual power plugs or use the power bus (see section 4.1). Segregate hazardous- and safe-area wiring into separate trunking or looms wherever possible to avoid errors and maintain a tidy installation.
  • Page 10: Earth Rail And Tagging Accessories

    3 .4 Earth rail and tagging accessories This section explains how to specify and assemble earth rail and tagging strip accessories for the MTL 9493-PS-XXX power supplies. The accessories consist of mounting brackets, earth rails, tagging strips and associated parts. They provide facilities for earthing, terminating cable screens and tagging (identifying) the positions of individual units.
  • Page 11 THR2 TGL57 ERB57S IMB57 TAG57 Snap off extension when using IMB57 as central support ERB57 10mm Earth 14mm clamp Earth-rail clamp ETM7 Push ERL7 fastener ERB57S in upper ERB570 position ERB57S in lower ERL7 position IMB57 ETM7 TGL57 HAZ1-3 HAZ4-6 TAG57 Figure 3 .4: Assembly drawing showing part numbers Figure 3 .5: Mounting details...
  • Page 12: Assembly

    3 .5 Assembly 3 .5 . 1 Fitting earth rails a) In upper position Before fitting insulating mounting blocks IMB57 , check that the swing nuts in the base of each unit are turned back into the moulding. Locate the mounting blocks on the DIN rail in the chosen position and tighten the screws (see figure 3.11).
  • Page 13: Completed Assemblies

    3 .5 .3 Completed assemblies Figure 3.12 illustrates a complete assembly of MTL 9493-PS-XXX power supplies using the accessories mentioned above. The broken-line boxes either side of the assembly represent cable trunking, and the accompanying dimensions represent the minimum spacing between trunking and assemblies. Figure 3 .12: MTL 9493-PS-XXX power supplies-...
  • Page 14: Backplane Mounting Variant

    BACKPLANE MOUNTING VARIANT PLEASE NOTE: The backplane mounting variant is only available by prior special arrangement . Please contact MTL product line to discuss . The alternative to DIN-rail mounting is to use a standard MTL backplane that accommodates 8 modules with 24V dc dual redundant power supplies.
  • Page 15 M4 x 20mm Fixing Screws screw(1) G-section G-section T-section Locking washer (2) T-section End stop (13) (12) (13) (12) MTL4500 (11) Plain washer (3) backplane Mounting hole A M4 x 10mm spacer(5) Retaining Washer (6) Figure 4 .2: Surface mounting procedure Figure 4 .5: Mounting end stops onto DIN rail Centre A Centre A...
  • Page 16: Surface Mounting - With Kit Sms01

    4 .3 . 1 Surface mounting – with kit SMS01 See Figures 4.1 and 4.2. Select four M4 x 20mm screws. Prepare holes in the surface at centres A, tapping these if retaining nuts are not required (Figure 4.1). Place a locking washer (2) and a plain washer (3) over each M4 x 20mm screw (1) (Figure 4.2).
  • Page 17 Tagging strip Retaining PWR1 PWR2 – tie (7) Primary Secondary Power Power Supply Supply SKT 1 SKT 2 0V PWR1 0V PWR2 Figure 4 .11: Power supply connections Figure 4 .8: Attaching and swivelling a tagging-strip P W R 1 Plastic rivet (7) Earth rail (5) Earth rail...
  • Page 18: Backplanes - Earth Rails

    4 .5 Backplanes - earth rails Optional earth rails are available for backplanes (kit ERK08). Cable screens from hazardous-area circuits, or spare pairs from a multicore cable, are connected to the terminals on the earth rails, which are mounted on the backplane at about the same height as the front of the modules, close to the hazardous-area connectors.
  • Page 19 12mm Figure 4 .13: Wiring hazardous-area power output plugs Figure 4 .15: Fitting power supplies to backplane Hazardous area power connectors Haz 1-3 ia output 0ther models available Figure 4 .14: Key elements of the MTL 9493-PS-XXX power supply Figure 4 .16: Removing power supplies from backplane INM 9493-PS-XXX Rev 2...
  • Page 20: Environmental

    ENVIRONMENTAL Operating Temperature -40°C…+70°C Storage Temperature –40°C…+70°C Humidity 5…95% RH, non condensing WASTE REMOVAL INFORMATION The electronic equipment within must not be treated as general waste. By ensuring that this product is disposed of correctly you will be helping to prevent potentially negative consequences for the environment and human health, which could otherwise be caused by incorrect waste handling of this product.
  • Page 21: Atex & Iecex Certification Information

    ATEX & IECEx CERTIFICATION INFORMATION The following information is in accordance with the Essential Health and Safety Requirements (Annex II) of the EU Directive 2014/34/EU [the ATEX Directive - safety of apparatus] and is provided for those locations where the ATEX Directive is applicable. General This equipment must only be installed, operated and maintained by competent personnel.
  • Page 22 Marking Each device is marked in accordance with the Directive and CE marked with the Notified Body Identification Number. This information applies to products manufactured during or after the year 2010. Figure 8 .1 MTL 9493-PS-XXX product label INM 9493-PS-XXX Rev 2...
  • Page 23 This page left intentionally blank INM 9493-PS-XXX Rev 2...