Ups Communications Interface Port - Eaton Powerware Prestige Series 1500 VA Installation And Operator's Manual

Table of Contents

Advertisement

Communication

UPS Communications Interface Port

In addition to configuring the UPS for specific communication options,
you must also ensure proper use of the serial port when connecting the
UPS to your network or monitoring equipment.
Use only the pins specified for your communications configuration. The
use of any additional pins for any of the following interfaces can cause
interference with system communications.
Even though your network uses the specified signal lines, the pins
assigned to these signals at the network end of the cable may vary with
those of the UPS serial port. The connector body and style may vary as
well.
The UPS serial port complies with EIA RS-232 standards. RS-232
specifies a maximum cable length of 50 ft (15m). See Figure 20 for the
location of the serial port.
66
Powerware
®
Prestige Series Installation and Operator's Manual for IBM Applications (650 VA - 1500 VA) Uncontrolled Copy
The serial port LAN contacts are transistors and are rated at a maximum current of
50 mA and a maximum of +40 Vdc. Do not exceed these ratings or apply any
negative voltage or AC voltage to these contacts; otherwise, damage may occur to
your UPS.
NOTE Standard, pin-for-pin cables may not work correctly. Consult your network
software or server manuals for system shutdown pin assignments.
Serial
Port
UPS Rear Panel
C A U T I O N
Figure 20. Serial Port Location
Serial Port Detail