UPS with PPDM Startup for 208V-240V Models

To start up the UPS for 208V-240V models:
1. If you are connecting the UPS to an AS/400, the QUPSDLYTIM
system value for the UPS Monitoring feature should be set. See
"UPS Monitoring" on page 54 for instructions.
2. Confirm the Bypass switch on the PPDM rear panel is in the
NORMAL position (see Figure 9 on page 45).
3. Plug the input power supply cord (use the AS/400 line cord)
into the utility input connector on the PPDM rear panel.
4. Plug the other end of the power supply cord into a grounded,
three-wire, AC receptacle that has been wired in accordance
with national wiring rules.
NOTE Steps 5 through 8 are for changing the output voltage. The output voltage is
factory-configured for 230V. If you do not need to change the output voltage, skip to
Step 9.
5. Press the Output
All indicators flash simultaneously.
6. Press and hold the Output On button until the alarm beeps
again.
Two indicators, corresponding with the current setting, remain
flashing. The output voltage is factory-configured for 230V.
OVERLOAD
SITE FAULT
OVERTEMP
BATTERY
SELF TEST
7. Press the Output
voltage options, top to bottom. Each time you press the button,
the UPS beeps and the next two indicators flash.
Off button until the alarm beeps.
240V
230V
Figure 10. Output Voltage Indicators
Off button to scroll through the output
Installation
220V
208V
47