Resetting The Ups; Silencing The Alarm - Eaton Powerware Prestige Series 1500 VA Installation And Operator's Manual

Table of Contents

Advertisement

Condition
BATTERY
BATTERY
BATTERY
SELF TEST

Resetting the UPS

To reset the UPS while an alarm condition is present, press the
Output On button until the UPS alarm beeps.

Silencing the Alarm

To silence the alarm for an existing fault, press and hold the
Output On button for one second. The alarm becomes quiet.
If UPS status changes, the alarm beeps, overriding previous alarm
silencing. Press the Output On button again to silence the alarm.
Powerware
®
Prestige Series Installation and Operator's Manual for IBM Applications (650 VA - 1500 VA) Uncontrolled Copy
Possible Cause
Weak battery while in Normal
mode. The alarm beeps.
Battery breaker is open (O).
Battery cabinet is not properly
connected to the UPS.
Weak battery while in Bypass
mode.
Self Test failure. UPS internal
problem.
Action
Allow the battery to charge for 24 hours,
then retest. Have batteries replaced if
condition persists.
Verify that the battery circuit breaker is in
the ON (
) position.
|
Verify that the battery cords are
connected.
This usually indicates that the batteries
need replacing or the UPS requires service.
Contact your service representative.
The UPS may switch to Bypass mode,
depending on the circumstances.
Reset the UPS by pressing the Output
button until the alarm beeps.
Contact your service representative if
condition persists.
Troubleshooting
On
|
75

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Powerware prestige series 650 va

Table of Contents